Panel Design & Calculate Size of Bus bar
Example: Calculate Size of Bus bar having Following Details
- Bus bar Current Details:
- Rated Voltage = 415V,50Hz ,
- Desire Maximum Current Rating of Bus bar =630Amp.
- Fault Current (Isc)= 50KA ,Fault Duration (t) =1sec.
- Bus bar Temperature details:
- Operating Temperature of Bus bar (θ)=85°C.
- Final Temperature of Bus bar during Fault(θ1)=185°C.
- Temperature rise of Bus Bar Bar during Fault (θt=θ1-θ)=100°C.
- Ambient Temperature (θn) =50°C.
- Maximum Bus Bar Temperature Rise=55°C.
- Enclosure Details:
- Installation of Panel= Indoors (well Ventilated)
- Altitude of Panel Installation on Site= 2000 Meter
- Panel Length= 1200 mm ,Panel width= 600 mm, Panel Height= 2400 mm
- Bus bar Details:
- Bus bar Material= Copper
- Bus bar Strip Arrangements= Vertical
- Current Density of Bus Bar Material=1.6
- Temperature Co efficient of Material Resistance at 20°c(α20)= 0.00403
- Material Constant(K)= 1.166
- Bus bar Material Permissible Strength=1200 kg/cm2
- Bus bar Insulating Material= Bare
- Bus bar Position= Edge-mounted bars
- Bus bar Installation Media= Non-ventilated ducting
- Bus bar Artificial Ventilation Scheme= without artificial ventilation
- Bus bar Size Details:
- Bus bar Width(e)= 75 mm
- Bus bar Thickness(s)= 10 mm
- Number of Bus Bar per Phase(n)= 2 No
- Bus bar Length per Phase(a)= 500 mm
- Distance between Two Bus Strip per Phase(e)= 75 mm
- Bus bar Phase Spacing (p)= 400 mm
- Total No of Circuit= 3 No.
- Bus bar Support Insulator Detail:
- Distance between insulators on Same Phase(l)= 500 mm
- Insulator Height (H)= 100 mm
- Distance from the head of the insulator to the bus bar center of gravity (h)= 5 mm
- Permissible Strength of Insulator (F’)=1000 Kg/cm2
Calculation:
(1) De rating Factors for Bus bar:
- (1) Per Phase Bus Strip De rating Factor (K1):
- Bus bar Width(e) is 75mm and Bus bar Length per Phase(a) is 500mm so e/a is 75/500=0.15
- No of Bus bar per phase is 2 No’s.
- From following table value of de rating factor is 1.83
Number of Bus Bar Strip per Phase (K1)
| |||
e/a | No of Bus Bar per Phase | ||
1 | 2 | 3 | |
0.05 | 1 | 1.63 | 2.4 |
0.06 | 1 | 1.73 | 2.45 |
0.08 | 1 | 1.76 | 2.5 |
0.1 | 1 | 1.8 | 2.55 |
0.12 | 1 | 1.83 | 2.6 |
0.14 | 1 | 1.85 | 2.63 |
0.16 | 1 | 1.87 | 2.65 |
0.18 | 1 | 1.89 | 2.68 |
0.2
| 1 | 1.91 | 2.7 |
- (2) Bus bar Insulating Material De rating Factor (K2)
- Bus bar having No insulating material. It is Bare so following Table
- De rating Factor is 1.
Bus Bar Insulating Material (K2): | De rating Factor |
Bare | 1 |
PVC Sleeving | 1.2 |
Painted | 1.5 |
- (3) Bus bar Position De rating Factor (K3)
- Bus bar Position is Edge-mounted bars so following Table
- De rating Factor is 1
Bus Bar Position(K3): | De rating Factor |
Edge-mounted bars | 1 |
1 bar base-mounted | 0.95 |
several base-mounted bars | 0.75 |
- (4) Bus bar Installation Media De rating Factor (K4)
- Bus bar Installation Media is Non-ventilated ducting so following Table
- De rating Factor is 0.8
Bus Bar Installation Media(K4): | De rating Factor |
Calm indoor atmosphere | 1 |
Calm outdoor atmosphere | 1.2 |
Non-ventilated ducting | 0.8 |
- (5) Bus bar Artificial Ventilation De rating Factor (K5)
- Bus bar Installation Media is Non-ventilated ducting so following Table
- De rating Factor is 0.9
Bus Bar Artificial Ventilation Scheme (K5): | De rating Factor |
without artificial ventilation | 0.9 |
with artificial ventilation | 1 |
- (6) Enclosure & Ventilation De rating Factor (K6)
- Bus bar Area per Phase = Bus width X Bus Thickness X Length of Bus X No of Bus bar per Phase
- Bus bar Area per Phase = 75x10xX500X2= 750000mm
- Total Bus bar Area for Enclosure= No of Circuit X( No of Phase + Neutral )X Bus bar Area per Phase
- Here we used Size of Neutral Bus is equal to Size of Phase Bus
- Total Bus bar Area for Enclosure=3X(3+1)X750000mm
- Total Bus bar Area for Enclosure=9000000 Sq.mm
- Total Enclosure Area= width X Height X Length
- Total Enclosure Area=1200x600x2400=1728000000 Sq.mm
- Total Bus bar Area for Enclosure / Total Enclosure Area =9000000/1728000000
- Total Bus bar Area for Enclosure / Total Enclosure Area=0.53%
- Bus bar Artificial Ventilation Scheme is without artificial ventilation so following Table
- De rating Factor is 0.95
Volume of Enclosure & Ventilation De rating Factor (K6) | |||
cross Section area of Bus bar/Total Bus Bar Area | Indoors ( Panel is well Ventilated) | Indoors ( Panel is Poorly Ventilated) | Outdoor |
0% | 0.95 | 0.85 | 0.65 |
1% | 0.95 | 0.85 | 0.65 |
5% | 0.9 | 0.7 | 0.6 |
10% | 0.85 | 0.65 | 0.5 |
- (7) Proxy Effect De rating Factor (K7)
- Bus bar Phase Spacing (p) is 400mm.
- Bus bar Width (e) is 75mm and Space between each bus of Phase is 75mm so
- Total Bus length of Phase with spacing =75+75+75+75+75=225mm
- Bus bar Phase Spacing (p) / Total Bus length of Phase with spacing = 400 / 225 =2
- From following Table De rating factor is 0.82
Proxy Effect (K7): | De rating Factor |
1 | 0.82 |
2 | 0.82 |
3 | 0.82 |
4 | 0.89 |
5 | 0.95 |
6 | 0.99 |
7 | 1 |
- (8) Altitude of Bus Bar installation De rating Factor (K8)
- Altitude of Panel Installation on Site is 2000 meter so following Table
- De rating Factor is 0.88
Altitude of installation site (Meter) (K8) | De rating Factor |
2200 | 0.88 |
2400 | 0.87 |
2500 | 0.86 |
2700 | 0.85 |
2900 | 0.84 |
3000 | 0.83 |
3300 | 0.82 |
3500 | 0.81 |
4000 | 0.78 |
4500 | 0.76 |
5000 | 0.74 |
- Total De rating Factor= K1XK2XK3Xk4Xk5Xk6Xk7Xk8
- Total De rating Factor =1.83x1x1x0.8×0.9×0.95×0.82×0.88
- Total De rating Factor =0.90
(2) Bus bar Size Calculation:
- Desire Current Rating of Bus bar (I2) =630 Amp
- Current Rating of Bus bar after De rating Factor (I1)= I2 X De rating Factor or I2 / De rating Factor
- Current Rating of Bus bar after De rating Factor (I1)=630×0.9
- Current Rating of Bus bar after De rating Factor (I1)=697Amp
- Bus bar Cross Section Area as per Current= Current Rating of Bus bar / Current Density of Material
- Bus bar Cross Section Area as per Current= 697 / 1.6
- Bus bar Cross Section Area as per Current= 436 Sq.mm
- Bus bar Cross Section Area as per Short Circuit= Isc X√ ((K/( θtx100)x(1+ α20xθ) xt
- Bus bar Cross Section Area as per Short Circuit= 50000X√ ((1.166/( 100×100)x(1+ 0.00403×85) x1
- Bus bar Cross Section Area as per Short Circuit=626 Sq.mm
- Select Higher Size for Bus bar Cross section area between 436 Sq.mm and 626 Sq.mm
- Final Calculated Bus Bar Cross Section Area =626 Sq.mm
- Actual Selected Bus bar size is 75×10=750 Sq.mm
- We have select 2 No’s of Bus bar per Phase hence.
- Actual Bus bar cross section Area per Phase =750×2= 1500 Sq.mm
- Actual Cross Section Area of Bus bar =1500 Sq.mm
- Actual Bus bar Size is Less than calculated Bus bar size.
(3) Forces generated on Bus Bar due to Short Circuit Current
- Peak electro-magnetic forces between phase conductors (F1) = 2X(l/d)X(2.5xIsc)2/100000000
- Total width of Bus bar per Phase(w)=75+75+75=225mm =2.25cm
- Bus bar Phase to Phase Distance (d)=400+225=625mm=6.25cm
- Peak electro-magnetic forces between phase conductors (F1) =2x(50/63)x(2.5×50000)2/100000000
- Peak electro-magnetic forces between phase conductors (F1)=250 Kg /cm2
- Peak electro-magnetic forces between phase conductors (F1)=2.5 Kg /mm2
- Actual Forces at the head of the Supports or Bus Bar (F)=F1X(H+h/H)
- Actual Forces at the head of the Supports or Bus Bar (F)=2.5x(100+5/100)
- Actual Forces at the head of the Supports or Bus Bar (F)= 3 Kg /mm2
- Permissible Strength of Insulator (F’) is 10 Kg/mm2
- Actual Forces at the head of the Supports or Bus Bar is less than Permissible Strength
- Forces on Insulation is in within Limits
(4) Mechanical strength of the bus bars
- Mechanical strength of the bus bars=(F1X i /12)x(1/ Modulus of inertia of a bus bar )
Value of Modulus of inertia of a bus bar or of a set of bus bars (i/v) | ||
No of Bus Strip per Phase | Vertical Bus Bar (cm3) | Horizontal Bus Bar (cm3) |
1 | 1.66 | 16.66 |
2 | 14.45 | 33.33 |
3 | 33 | 50 |
From above table Value of Modulus of inertia of a bus bar=14.45
- Mechanical strength of the bus bars=(250×50/12)X(1/14.45)
- Mechanical strength of the bus bars= 72 Kg/cm2
- Mechanical strength of the bus bars= 0.72 Kg/mm2
- Permissible Bus bar Strength is 12 Kg/mm2
- Actual Mechanical Strength is less than Permissible Strength
- Mechanical strength of Bus bar is in within Limit
(5) Temperature Rise Calculation
- Specified Maximum Temperature Rise (T1) is 35°c
- Calculated Maximum Temperature Rise (T2)=T/(log(I1/I2)1.64)
- Calculated Maximum Temperature Rise (T2)=35/(Log(697/630)1.64)
- Calculated Maximum Temperature Rise (T2)= 30°c
- Calculated Bus bar Temperature rise is less than Specified Max Temperature rise
- Temperature Rise is in within Limit
Results:
- Size of Bus bar = 2No’s 75x10mm per Phase.
- Total No of Feeder =3 No’s
- Total No’s of Bus bar = 6 No’s 75x10mm for Phase and 1No’s 75x10mm for Neutral.
- Forces at the head of the Supports or Bus Bar (F)= 3kg/mm2
- Mechanical strength of the bus bars= 0.7 Kg/mm2
- Maximum Temperature Rise=30°c
pls how do i download this? i mean the panels calculation tutorial...
ReplyDeleteLeave your email to make a direct contact with our executives
ReplyDeleteMobile No. : +91 9818292266
Email Id : nitin@brilltech.co.in
Electrical Panel Manufacturers
It is my first visit to your blog, and I am very impressed with the articles that you serve. Give adequate knowledge for me. Thank you for sharing useful material. I will be back for the more great post. zorgtaxirotterdam.nl
ReplyDeleteSolar panels are an investment in a more sustainable and resilient future. Solar company Los angeles
ReplyDelete