Welcome to [Dunia Electrical] >>Download Software ETAP disini >>Daftar Training ETAP disini

Panel Design & Calculate Size of Bus bar

Example: Calculate Size of Bus bar having Following Details
  • Bus bar Current Details:
  • Rated Voltage = 415V,50Hz ,
  • Desire Maximum Current Rating of Bus bar =630Amp.
  • Fault Current (Isc)= 50KA ,Fault Duration (t) =1sec.
  • Bus bar Temperature details:
  • Operating Temperature of Bus bar (θ)=85°C.
  • Final Temperature of Bus bar during Fault(θ1)=185°C.
  • Temperature rise of Bus Bar Bar during Fault (θt=θ1-θ)=100°C.
  • Ambient Temperature (θn) =50°C.
  • Maximum Bus Bar Temperature Rise=55°C.
  • Enclosure Details:
  • Installation of Panel= Indoors (well Ventilated)
  • Altitude of Panel Installation on Site= 2000 Meter
  • Panel Length= 1200 mm ,Panel width= 600 mm, Panel Height= 2400 mm
  • Bus bar Details:
  • Bus bar Material= Copper
  • Bus bar Strip Arrangements= Vertical
  • Current Density of Bus Bar Material=1.6
  • Temperature Co efficient of Material Resistance at 20°c(α20)= 0.00403
  • Material Constant(K)= 1.166
  • Bus bar Material Permissible Strength=1200 kg/cm2
  • Bus bar Insulating Material= Bare
  • Bus bar Position= Edge-mounted bars
  • Bus bar Installation Media= Non-ventilated ducting
  • Bus bar Artificial Ventilation Scheme= without artificial ventilation
  • Bus bar Size Details:
  • Bus bar Width(e)= 75 mm
  • Bus bar Thickness(s)= 10 mm
  • Number of Bus Bar per Phase(n)= 2 No
  • Bus bar Length per Phase(a)= 500 mm
  • Distance between Two Bus Strip per Phase(e)= 75 mm
  • Bus bar Phase Spacing (p)= 400 mm
  • Total No of Circuit= 3 No.
  • Bus bar Support Insulator Detail:
  • Distance between insulators on Same Phase(l)= 500 mm
  • Insulator Height (H)= 100 mm
  • Distance from the head of the insulator to the bus bar center of gravity (h)= 5 mm
  • Permissible Strength of Insulator (F’)=1000 Kg/cm2

 Untitled

Calculation:

(1) De rating Factors for Bus bar:

  • (1) Per Phase Bus Strip De rating Factor (K1):
  • Bus bar Width(e) is 75mm and Bus bar Length per Phase(a) is 500mm so e/a is 75/500=0.15
  • No of Bus bar per phase is 2 No’s.
  • From following table value of de rating factor is 1.83
Number of Bus Bar Strip per Phase (K1)
e/aNo of Bus Bar per Phase
123
0.0511.632.4
0.0611.732.45
0.0811.762.5
0.111.82.55
0.1211.832.6
0.1411.852.63
0.1611.872.65
0.1811.892.68
0.2
11.912.7

  • (2) Bus bar Insulating Material De rating Factor (K2)
  • Bus bar having No insulating material. It is Bare so following Table
  • De rating Factor is 1.
Bus Bar Insulating Material (K2):De rating Factor
Bare1
PVC Sleeving1.2
Painted1.5

  • (3) Bus bar Position De rating Factor (K3)
  • Bus bar Position is Edge-mounted bars so following Table
  • De rating Factor is 1
Bus Bar Position(K3):De rating Factor
Edge-mounted bars1
1 bar base-mounted0.95
several base-mounted bars0.75

  • (4) Bus bar Installation Media De rating Factor (K4)
  • Bus bar Installation Media is Non-ventilated ducting so following Table
  • De rating Factor is 0.8
Bus Bar Installation Media(K4):De rating Factor
Calm indoor atmosphere1
Calm outdoor atmosphere1.2
Non-ventilated ducting0.8

  • (5) Bus bar Artificial Ventilation De rating Factor (K5)
  • Bus bar Installation Media is Non-ventilated ducting so following Table
  • De rating Factor is 0.9
Bus Bar Artificial Ventilation Scheme (K5):De rating Factor
without artificial ventilation0.9
with artificial ventilation1

  • (6) Enclosure & Ventilation De rating Factor (K6)
  • Bus bar Area per Phase = Bus width X Bus Thickness X Length of Bus X No of Bus bar per Phase
  • Bus bar Area per Phase = 75x10xX500X2= 750000mm
  • Total Bus bar Area for Enclosure= No of Circuit X( No of Phase + Neutral )X Bus bar Area per Phase
  • Here we used Size of Neutral Bus is equal to Size of Phase Bus
  • Total Bus bar Area for Enclosure=3X(3+1)X750000mm
  • Total Bus bar Area for Enclosure=9000000 Sq.mm
  • Total Enclosure Area= width X Height X Length
  • Total Enclosure Area=1200x600x2400=1728000000 Sq.mm
  • Total Bus bar Area for Enclosure / Total Enclosure Area =9000000/1728000000
  • Total Bus bar Area for Enclosure / Total Enclosure Area=0.53%
  • Bus bar Artificial Ventilation Scheme is without artificial ventilation so following Table
  • De rating Factor is 0.95
Volume of Enclosure & Ventilation De rating Factor (K6)
cross Section area of Bus bar/Total Bus Bar AreaIndoors ( Panel is well Ventilated)Indoors ( Panel is Poorly Ventilated)Outdoor
0%0.950.850.65
1%0.950.850.65
5%0.90.70.6
10%0.850.650.5

  • (7) Proxy Effect De rating Factor (K7)
  • Bus bar Phase Spacing (p) is 400mm.
  • Bus bar Width (e) is 75mm and Space between each bus of Phase is 75mm so
  • Total Bus length of Phase with spacing (w) =75+75+75+75+75=225mm
  • Bus bar Phase Spacing (p) / Total Bus length of Phase with spacing (w) = 400 / 225 =2
  • From following Table De rating factor is 0.82
Proxy Effect (K7):De rating Factor
10.82
20.82
30.82
40.89
50.95
60.99
71

  • (8) Altitude of Bus Bar installation De rating Factor (K8)
  • Altitude of Panel Installation on Site is 2000 meter so following Table
  • De rating Factor is 0.88
Altitude of installation site (Meter) (K8)De rating Factor
22000.88
24000.87
25000.86
27000.85
29000.84
30000.83
33000.82
35000.81
40000.78
45000.76
50000.74
  • Total De rating Factor= K1XK2XK3Xk4Xk5Xk6Xk7Xk8
  • Total De rating Factor =1.83x1x1x0.8×0.9×0.95×0.82×0.88
  • Total De rating Factor =0.90

(2) Bus bar Size Calculation:

  • Desire Current Rating of Bus bar (I2) =630 Amp
  • Current Rating of Bus bar after De rating Factor (I1)= I2 X De rating Factor or I2 / De rating Factor
  • Current Rating of Bus bar after De rating Factor (I1)=630×0.9
  • Current Rating of Bus bar after De rating Factor (I1)=697Amp
  • Bus bar Cross Section Area as per Current= Current Rating of Bus bar / Current Density of Material
  • Bus bar Cross Section Area as per Current= 697 / 1.6
  • Bus bar Cross Section Area as per Current= 436 Sq.mm
  • Bus bar Cross Section Area as per Short Circuit= Isc X√ ((K/( θtx100)x(1+ α20xθ) xt
  • Bus bar Cross Section Area as per Short Circuit= 50000X√ ((1.166/( 100×100)x(1+ 0.00403×85) x1
  • Bus bar Cross Section Area as per Short Circuit=626 Sq.mm
  • Select Higher Size for Bus bar Cross section area between 436 Sq.mm and 626 Sq.mm
  • Final Calculated Bus Bar Cross Section Area =626 Sq.mm
  • Actual Selected Bus bar size is 75×10=750 Sq.mm
  • We have select 2 No’s of Bus bar per Phase hence.
  • Actual Bus bar cross section Area per Phase =750×2= 1500 Sq.mm
  • Actual Cross Section Area of Bus bar =1500 Sq.mm
  • Actual Bus bar Size is Less than calculated Bus bar size.

(3) Forces generated on Bus Bar due to Short Circuit Current

  • Peak electro-magnetic forces between phase conductors (F1) = 2X(l/d)X(2.5xIsc)2/100000000
  • Total width of Bus bar per Phase(w)=75+75+75=225mm =2.25cm
  • Bus bar Phase to Phase Distance (d)=400+225=625mm=6.25cm
  • Peak electro-magnetic forces between phase conductors (F1) =2x(50/63)x(2.5×50000)2/100000000
  • Peak electro-magnetic forces between phase conductors (F1)=250 Kg /cm2
  • Peak electro-magnetic forces between phase conductors (F1)=2.5 Kg /mm2
  • Actual Forces at the head of the Supports or Bus Bar (F)=F1X(H+h/H)
  • Actual Forces at the head of the Supports or Bus Bar (F)=2.5x(100+5/100)
  • Actual Forces at the head of the Supports or Bus Bar (F)= 3 Kg /mm2
  • Permissible Strength of Insulator (F’) is 10 Kg/mm2
  • Actual Forces at the head of the Supports or Bus Bar is less than Permissible Strength
  • Forces on Insulation is in within Limits

(4) Mechanical strength of the bus bars

  • Mechanical strength of the bus bars=(F1X i /12)x(1/ Modulus of inertia of a bus bar )
Value of Modulus of inertia of a bus bar or of a set of bus bars (i/v)
No of Bus Strip per PhaseVertical Bus Bar (cm3)Horizontal Bus Bar (cm3)
11.6616.66
214.4533.33
33350
 From above table Value of Modulus of inertia of a bus bar=14.45
  • Mechanical strength of the bus bars=(250×50/12)X(1/14.45)
  • Mechanical strength of the bus bars= 72 Kg/cm2
  • Mechanical strength of the bus bars= 0.72 Kg/mm2
  • Permissible Bus bar Strength is 12 Kg/mm2
  • Actual Mechanical Strength is less than Permissible Strength
  • Mechanical strength of Bus bar is in within Limit

(5) Temperature Rise Calculation

  • Specified Maximum Temperature Rise (T1) is 35°c
  • Calculated Maximum Temperature Rise (T2)=T/(log(I1/I2)1.64)
  • Calculated Maximum Temperature Rise (T2)=35/(Log(697/630)1.64)
  • Calculated Maximum Temperature Rise (T2)= 30°c
  • Calculated Bus bar Temperature rise is less than Specified Max Temperature rise
  • Temperature Rise is in within Limit

Results:

  • Size of Bus bar = 2No’s 75x10mm per Phase.
  • Total No of Feeder =3 No’s
  • Total No’s of Bus bar = 6 No’s 75x10mm for Phase and 1No’s 75x10mm for Neutral.
  • Forces at the head of the Supports or Bus Bar (F)= 3kg/mm2
  • Mechanical strength of the bus bars= 0.7 Kg/mm2
  • Maximum Temperature Rise=30°c
Share this Post Facebook Twitter Google+ WhatsApp

Subscribe to receive free email updates:

4 Responses to "Panel Design & Calculate Size of Bus bar"

  1. pls how do i download this? i mean the panels calculation tutorial...

    ReplyDelete
  2. Leave your email to make a direct contact with our executives
    Mobile No. : +91 9818292266
    Email Id : nitin@brilltech.co.in
    Electrical Panel Manufacturers

    ReplyDelete
  3. It is my first visit to your blog, and I am very impressed with the articles that you serve. Give adequate knowledge for me. Thank you for sharing useful material. I will be back for the more great post. zorgtaxirotterdam.nl

    ReplyDelete
  4. Solar panels are an investment in a more sustainable and resilient future. Solar company Los angeles

    ReplyDelete

Loading...