Bahan Kuliah Elektro || Ebook Electrical Distribution Engineering by Anthony J. Pansini
Although
there is no “typical” electric power system, a diagram including the several
components that are usually to be found in the makeup of such a system is shown
in Figure 1-1; particular attention should be paid to those elements which will
make up the component under discussion, the distribution system.
While
the energy flow is obviously from the power generating plant to the consumer, it
may be more informative for our purposes to reverse the direction of
observation and consider events from the consumer back to the generating source.
Energy
is consumed by users at a nominal utilization voltage that may range generally
(in the United States) from 110 to 125 V, and from 220 to 250 V (for some large
commercial and industrial users, the nominal figures are 277 and 480 V). It flows
through a metering device that determines the billing for the consumer, but
which may also serve to obtain data useful later for planning, design, and
operating purposes. The metering equipment usually includes a means of
disconnecting the consumer from the incoming supply should this become
necessary for any reason.
The
energy flows through conductors to the meter from the secondary mains (if any); these conductors are referred to as
the consumer’s service, or sometimes also as the service drop.
Several
services are connected to the secondary mains; the secondary mains now serve
as a path to the several services from the distribution transformers which
supply them.
At
the transformer, the voltage of the energy being delivered is reduced to the
utilization voltage values mentioned earlier from higher primary line voltages that may range from 2200 V to as high as
46,000 V.
The
transformer is protected from overloads
and faults by fuses or so called weak
links on the high-voltage side; the
latter also usually include circuit-breaking
devices on the low-voltage side. These operate to disconnect the
transformer in the event of overloads or faults. The circuit
Figure 1-1. Typical electric system showing operational divisions. Note overlap of divisions.
breakers (where they exist) on the secondary,
or low-voltage, side operate only if the condition is caused
by faults or overloads in the secondary mains, services, or consumers’ premises; the primary fuse or weak link in
addition operates in the event of a failure
within the transformer itself.
If
the transformer is situated on an overhead system, it is also protected from
lightning or line voltage surges by a surge arrester, which drains the voltage
surge to ground before it can do damage to the trans- former.
The
transformer is connected to the primary circuit, which may be a lateral or spur consisting of one
phase of the usual three-phase primary main. This is done usually through a line or sectionalizing fuse, whose function is to disconnect the lateral
from the main in the event of fault or overload in the lateral. The lateral
conductors carry the sum of the energy components flowing through each of the
transformers, which represent not only the energy used by the consumers
connected thereto, but also the energy lost in the lines and transformers to that point.
The
three-phase main may consist of several three-phase branches connected
together, sometimes through other line or sectionalizing fuses, but sometimes
also through switches. Each of the branches may have several single-phase
laterals connected to it through line or sectionalizing fuses.
Where
single-phase or three-phase overhead lines run for any considerable distance
without distribution transformer installations connected to them, surge
arresters may be installed on the lines for protection, as described earlier.
Some
three-phase laterals may sometimes also be connected to the three-phase main
through circuit reclosers. The
recloser acts to disconnect the lateral from the main should a fault occur on
the lateral, much as a line or sectionalizing fuse. However, it acts to
reconnect the lateral to the main, re-energizing it one or more times after a
time delay in a predetermined sequence before remaining open permanently.
This is done so that a fault which may be only of a temporary nature, such as a
tree limb falling on the line, will not cause a prolonged interruption of
service to the consumers connected to the lateral.
The
three-phase mains emanate from a distribution
substation, supplied from a bus in
that station. The three-phase mains, usually referred to as a circuit or feeder, are connected to
the bus through a protective circuit breaker and sometimes a voltage
regulator. The voltage regulator is usually
a modified form of transformer and serves to maintain outgoing voltage within a
predetermined band or range on the circuit or feeder as its load varies. It is sometimes placed
electrically in the substation circuit so that it regulates the voltage of the
entire bus rather than a single outgoing circuit
or feeder, and sometimes along the route of a feeder for
partial feeder regulation. The circuit breaker in the feeder acts to disconnect
that feeder from the bus in the event of overload or fault on the outgoing or
distribution feeder.
The
substation bus usually supplies several distribution feeders and carries the
sum of the energy supplied to each of the distribution feeders connected to it.
In turn, the bus is supplied through one or more transformers and associated
circuit breaker protection. These substation transformers step down the voltage
of their supply circuit, usually called the sub transmission system, which operates at voltages usually from 23,000 to 138,000 V.
The
sub transmission systems may supply several distribution substations and may act
as tie feeders between two or more
substations that are either of the bulk
power or transmission type or of the distribution type. They may also be
tapped to supply some distribution load, usually through a circuit breaker, for
a single consumer, generally an industrial plant or a commercial consumer having
a substantially large load.
The
transmission or bulk power substation serves much the same purposes as a
distribution substation, except that, as the name implies, it handles much greater amounts of energy:
the sum of the energy individually supplied to the sub transmission lines and
associated distribution substations and losses. Voltages at the transmission substations are reduced to outgoing sub transmission line voltages from
transmission voltages that may range from 69,000 to upwards of 750,000 V.
The
transmission lines usually emanate from another substation associated with a
power generating plant. This last substation operates in much the same manner
as other substations, but serves to step up to transmission line voltage values
the voltages produced by the generators. Because of material and insulation
limitations, generator voltages may range from a few thousand volts for older
and smaller units to some 20,000
volts for more recent, larger ones. Both buses and transformers in these substations
are protected by circuit breakers, surge arresters, and other protective devices.
In
all the systems described, conductors should be large enough that the energy
loss in them will not be excessive, nor the loss in voltage so great that
normal nominal voltage ranges at the consumers’ services cannot be maintained.
In
some instances, voltage regulators and capacitors are installed at strategic
points on overhead primary circuits as a means of compensating for voltage
drops or losses, and incidentally help in holding down Energy losses in the conductors.
In
many of the distribution system arrangements, some of the several elements
between the generating plant and the consumer may not be necessary.
In a relatively small area, such as a small town, that is served by a power plant situated in or
very near the service area, the distribution feeder may emanate directly from
the power plant bus, and all other elements may be eliminated, as indicated in
Figure 1-2. This is perhaps one extreme; in many other instances only some of
the other elements may not be necessary; e.g., a similar small area somewhat
distant from the generating plant may find it necessary to install a
distribution substation supplied by a transmission line of appropriate voltage only.
Figure 1-2. “Abbreviated” electric system.
In the case of areas of high load density and rather severe
service reliability requirements, the distribution system becomes more complex and more expensive. The several secondary mains to which the consumers’
services are connected may all be connected into a mesh or network. The transformers
supplying these secondary mains or network are supplied from several
different primary feeders, so that if one or more of these feeders is out of
service for any reason, the secondary network is supplied from the remaining
ones and service to the consumers is not interrupted. To prevent a
feeding-back from the energized secondary network through the transformers
connected to feeders out of service (thereby energizing the primary and
creating unsafe conditions), automatically operated circuit breakers, called network protectors, are connected
between the secondary network and the secondary of the transformers; these open
when the direction of energy flow is reversed. The two examples cited here are
perhaps the two extremes in the design of distribution systems, the first the
simplest, the latter the most complex. There are many variations in between
these, and the basic ones will be
described in their appropriate places.
Only
distribution systems, however, will be the subject of further description and
discussion in this book. In general, these include the distribution substation,
primary feeders, transformers, secondary mains, services, and other elements
between the substation and the consumers’ points of service.
Download disini
quoted from Anthony J. Pansini's book - Electrical Distribution Engineering Third Edition
0 Response to "Bahan Kuliah Elektro || Ebook Electrical Distribution Engineering by Anthony J. Pansini"
Post a Comment